    English Chinese Indonesian Kazakh Russian Spanish Thai French German Arabic Italian Malay Persian Vietnamese Yucatec Maya Twi (Akan) Tswana Tsonga Tigrinya Tetum Swati Silesian Sicilian Shan Seychellois Creole Sanskrit Blood Rundi Romani Quechua Punjabi (Shamuki) Papiamento Pangasinan Oromo Occitan Nuer Northern Sotho (Sepéti) Nepali (Newari) Ndebele (Southern) Mizo Minan Meitei (Manipuri) Steppe Mari Malay (Jawi) Makassar Maithili Luo Lombard Lingala Limburgish Ligurian Latgale Kurdish (Sorani) Kryo Konkani Kituba Kiga Pampanga Iloko Hunsrück Hiligaynon Hakachin Guarani Ganda (Luganda) Ga Fula Fijian Ewe Dzongkha Doumbe Dogra Divi Sewing Crimean Tatar Chuvash Cantonese Buryat Breton Bicol Bhojpuri Betawi Pemba Batak Toba Bataximau Longong Batak Karo Bashkir Bambara Balinese Aymara Awadish Assamese Alur Acholi Acehnese Abkhaz Uyghur Turkmen Oriya Tatar Kinyarwanda Zulu Yoruba Yiddish Xhosa Welsh Uzbek Urdu Ukrainian Telugu Tamil Tajik Swahili Sundanese Sindhi Shona Scots Gaelic Samoan Somali Slovenian Slovak Sinhala Sesotho Serbian Punjabi Pashto Norwegian Nepali Burmese Mongolian Marathi Maori Maltese Malayalam Malagasy Macedonian Luxembou.. Lithuanian Latvian Latin Kyrgyz Kurdish Khmer Kannada Javanese Igbo Icelandic Hungarian Hmong Hebrew Hawaiian Hausa Haitian Gujarati Georgian Galician Frisian Finnish Filipino Estonian Dutch Croatian Corsican Chichewa Cebuano Bulgarian Bosnian Bengali Belarusian Azerbaijani Armenian Amharic Albanian Lao Hindi Esperanto Catalan Basque Polish Swedish Afrikaans Czech Romanian Danish Turkish Greek Irish Korean Japanese Portuguese Chinese Traditional
    More Language
    Leave Your Message

    Medical Direct Expansion Air Handling Unit

    Use interior wall panels that are corrosion-resistant and antibacterial.. Use dust - free, rust - free PTC electric heating. Limit coil face air velocity to 2 m/s and use stainless - steel water pans.
    Choose dry steam or electrode - type humidifiers, and equip fans with frequency converters. Use disposable filters. Prioritize humidity control with an outlet limit of 75%. Include features like fan delay shutdown and control panel linkage.
    Select UV germicidal lamps for relevant sections, and add ozone generators or nano photocatalytic materials at the outlet. Use micro - perforated plates for sound attenuators.

    Model:  ZYJ

    Airflow range: 3000m³/h to 30000m³/h
    Refrigerant type: R410A; R134a; R32

    Advantage

    iocn_2

    Design for flexibility

    index_icon-4

    stability

    index_icon-1

    energy conservation

    Technical Parameter

    Inner Wall Material Requirements
    Electric Heating Element Requirements
    Coil and Water Pan Design Requirements
    Humidifier Selection and Design Requirements
    Filter Requirements
    Unit Control Requirements
    Sterilization Equipment Selection Suggestions
    Sound Attenuator Material Requirements

    Inner Wall Material Requirementstheme

    The interior wall panels are made of anti-corrosion and antibacterial materials to meet the anti-rust requirements. resistance to disinfectant corrosion, and prevention of bacterial growth.

    Electric Heating Element Requirementstheme

    The electric heating should use a dust-free, rust-free, and non-peeling PTC type or other similar performance forms.

    Coil and Water Pan Design Requirementstheme

    The air velocity through the coil face should not exceed 2 m/s, and the cross-sectional air velocity should be uniform. The water pan must be made of stainless steel.

    Humidifier Selection and Design Requirementstheme

    Humidifiers should use dry steam or electrode-type humidifiers, avoiding wet film and other enthalpy humidification methods to ensure no water remains in the humidifier after shutdown, eliminating bacterial growth. Fans can be equipped with frequency converters for air volume adjustment to meet various customer requirements.

    Filter Requirementstheme

    Filters must be disposable and not reusable.

    Unit Control Requirementstheme

    The unit control should adopt a humidity control priority scheme: the relative humidity of the air at the outlet should not exceed 75%. After shutdown, the fan should delay shutdown to ensure the coil is dried. It should also have features such as operating room control panel linkage, duty fan frequency conversion or dual-speed operation to ensure pressure difference, automatic restart after power failure, and other related requirements.

    Sterilization Equipment Selection Suggestionstheme

    Ultraviolet germicidal lamps can be selected for the cooling section and the outlet section, and ozone generators or nano photocatalytic materials can be added to the outlet section. These are effective in killing bacteria in the air.

    Sound Attenuator Material Requirementstheme

    The sound attenuator material should be micro-perforated plates, without glass wool to prevent glass wool fiber pollution of the air conditioning environment.